Firemaster 607 was designed
for enhanced solubility in lung tissues. Rats
have been exposed 6 hours a day, 5 days a week
during 2 years at an average concentration
of 200 F/ml (about 200 to 300 times higher
than the concentration found in production
plants) without showing any significant increase
in lung tumours or fibrosis.
General Properties
| Colour |
White
with key production data printed on
Blanket surface. Layer of aluminiun
foil on other surface |
| Linear
Shrinkage ( 24 hrs @1000 deg C) |
<1% |
| Loss
on Ignition (5 hrs @ 1000 deg C) |
<0.1% |
| Foil
Characteristics |
40
micron thick aluminium with sodium
silicate glue |
| Foil
Peeling Force |
4N
for Water Repellent Blanket
6N for Non-Water
Repellent Blanket
|
Fire Protection Properties
Non Combustibility:
IMO A472 (12) 1984
All other properties
of FIREMASTER 607 Blanket will be as the ceramic
fibre based FIREMASTER Blanket, which are detailed
in the following sections.
Thermal Insulation Properties
FIREMASTER 607 provides good
thermal insulation over its entire operating
temperature range.
Thermal Conductivity Data
|
Mean Temperature
(
deg C)
|
64 kg/m³ density
|
96 kg/m³ density
|
128 kg/m³ density
|
160 kg/m³ density
|
192 kg/m³ density
|
| 200 |
0.07 |
0.06 |
0.06 |
0.06 |
0.06 |
| 300 |
0.09 |
0.08 |
0.08 |
0.07 |
0.07 |
| 400 |
0.12 |
0.11 |
0.10 |
0.09 |
0.09 |
| 500 |
0.17 |
0.14 |
0.13 |
0.12 |
0.11 |
| 600 |
0.22 |
0.17 |
0.16 |
0.15 |
0.14 |
For insulation under ambient
conditions the following maximum thermal resistance
(R value) figures may be used for calculation
of overall thermal transmittance (U value).
|
Thickness of Blanket
|
25mm
|
38 mm
|
50 mm
|
75 mm
|
100 mm
|
|
R
Value
M
K/W
|
0.73
|
1.11
|
1.46
|
2.19
|
2.92
|
Basis: Thermal Conductivity
of 96 kg/m³ density measured at 20 Deg C to
BS 874 of 0.0342 W/MK.
AVAILABILITY
Firemaster Alu-40 Blanket
607 is available in a wide variety of thickness
and densities. See the table below for details.
Standard size is 610mm or
1220mm wide.
With Standard Firemaster
607 Blanket as the substrate
|
Density Kg/m
|
6mm
|
13mm
|
20mm
|
25mm
|
38mm
|
50mm
|
63mm
|
70mm
|
|
64
|
NO
|
YES
|
YES
|
YES
|
YES
|
YES
|
NO
|
NO
|
|
96
|
NO
|
YES
|
YES
|
YES
|
YES
|
YES
|
YES
|
NO
|
|
128
|
YES
|
YES
|
YES
|
YES
|
YES
|
YES
|
NO
|
NO
|
|
160
|
YES
|
YES
|
YES
|
YES
|
YES
|
NO
|
NO
|
NO
|
|
Roll
Length
|
21.60m
|
14.64m
|
9.76m
|
7.32m
|
4.88m
|
3.66m
|
2.3m**
|
2.3m**
|
* Roll length may vary, please
check with Thermal Ceramics
** 2300mm lengths are supplied
as flat slabs not rolls
With Firemaster Water Repellent
607 Blanket as the substrate
|
Density kg/m³
|
13mm
|
20mm
|
25mm
|
38mm
|
50mm
|
63mm
|
70mm
|
|
96
|
NO
|
NO
|
YES
|
YES
|
YES
|
YES
|
NO
|
|
128
|
NO
|
YES
|
YES
|
YES
|
YES
|
NO
|
NO
|
|
160
|
NO
|
YES
|
YES**
|
YES
|
NO
|
NO
|
NO
|
|
Roll
Length
|
14.64m
|
9.76m
|
7.32m
|
4.88m
|
3.66m
|
2.3m**
|
2.3m**
|
* Roll length may vary, please
check with Thermal Ceramics
** 2300mm lengths are supplied
as flat slabs not rolls
TYPICAL APPLICATIONS
- A class
and IMO HSC steel, aluminium and PVC composite
bulkhead and deck insulation in high sped
craft
- Upgrading
of fire performance of composite panels
to meet IMO room corner test requirements
- H
class and A class steel bulkhead and deck
fire protection for ships and offshore
platforms
- Hydrocarbon
and Jet fire protection of process pipes
- Hydrocarbon
and Jet fire protection of vessels
- Infill to fire doors and
cladding panels
- Construction joints
- Cellulosic
and hydrocarbon fire protection of structural
steelwork
- Ductwork
fire protection
- Cable
tray fire protection